Voltage Drop Calculator

Supply system
Conductor material

The voltage drop (3.13%) exceeds the 3% limit IEC 60364-5-52 Table G.52.1 recommends for a lighting circuit.

Calculated per IEC 60364-5-52 Annex G with the conductor resistivity in normal service (1.25 × the 20 °C value: copper 0.0225, aluminium 0.036 Ω·mm²/m) and a purely resistive load (cos φ = 1, reactance neglected).

Standard: IEC 60364-5-52 Annex G

Diagram
DVoltage drop7.20V
Drop (% of nominal)3.13%
Voltage at load222.8V

About this calculator

This calculator estimates the voltage drop over a single cable run — enter the supply system (single-phase 230V or three-phase 400V), the load current, the cable's one-way length, its conductor cross-section, and whether the conductor is copper or aluminium. It reports the drop in volts, the drop as a percentage of the nominal voltage, and the voltage actually arriving at the load.

The method is the one in IEC 60364-5-52 (in Lithuania LST HD 60364-5-52), Annex G. To size the cable and its circuit-breaker as well, use the cable cross-section calculator.

Formula

IEC 60364-5-52 Annex G:

u  = b × (ρ₁ × L / S × cos φ + λ × L × sin φ) × I

This calculator takes a resistive load, cos φ = 1, so the reactance term drops out:

single-phase:  ΔU = 2 × L × I × ρ₁ / S          (b = 2)
three-phase:   ΔU = √3 × L × I × ρ₁ / S         line-to-line, against 400 V

L is the cable's one-way length in metres, I the load current in amps, S the conductor cross-section in mm². A single-phase circuit counts the run's resistance twice — out on the line conductor, back on the neutral — hence the 2. For a balanced three-phase load the line-to-line drop uses √3 (Annex G's b = 1 against the 230 V phase voltage gives the same percentage).

ρ₁ is the conductor resistivity in normal service — Annex G takes it as 1.25 × the value at 20 °C, because a loaded cable runs warm:

copper:     ρ₁ = 0.0225 Ω·mm²/m
aluminium:  ρ₁ = 0.036  Ω·mm²/m
drop percent      = ΔU / nominal voltage × 100
voltage at load   = nominal voltage − ΔU

Nominal voltage is 230V for single-phase, 400V for three-phase.

Worked example

32A, 25m one-way, 4mm² copper, single-phase:

ΔU = 2 × 25 × 32 × 0.0225 / 4
   = 1600 × 0.0225 / 4
   = 36 / 4
   = 9.0 V

drop percent    = 9.0 / 230 × 100 = 3.91 %
voltage at load = 230 − 9.0 = 221.0 V

3.91% is over the 3% limit for a lighting circuit but within the 5% limit for other uses, so this example is shown with a warning, not a clean pass.

FAQ

Why 3% and 5%, specifically? IEC 60364-5-52 Table G.52.1 recommends, for an installation supplied directly from the public low-voltage network, a drop of at most 3% for lighting and 5% for other uses, measured from the origin of the installation (the meter) to the equipment. An installation with its own transformer or generator may go to 6% and 8%. The calculator warns above 3% and flags an error above 5%.

Does this calculator size the cable or select a breaker for me? No. It only reports the drop for the cross-section you already chose. The cable cross-section calculator selects the size and the circuit-breaker rating from the current-carrying capacity and checks this same drop.

Why does the drop change so much between copper and aluminium at the same cross-section? Aluminium's resistivity (0.036 Ω·mm²/m in service) is 1.6 times copper's (0.0225 Ω·mm²/m), so the same run in aluminium drops proportionally more voltage — this is why an aluminium conductor is usually one or two sizes larger than the copper conductor it replaces.

Why can't I choose aluminium below 10 mm²? The current IEC 60364-5-52 (2009, adopted in Lithuania as LST HD 60364-5-52) sets 10 mm² as the smallest aluminium conductor for cables in fixed power and lighting circuits (copper: 1.5 mm²) — the older 1993 edition allowed 2.5 mm², which is why that figure still circulates. Below 10 mm² the calculator stops with an error instead of computing a drop for a cable that is not allowed. At 10 mm² it shows a warning: aluminium needs terminals and connectors tested and approved for aluminium, and national wiring rules may require copper or a larger section.

Why is the resistivity 0.0225 and not the textbook 0.0175? 0.0175–0.018 Ω·mm²/m is copper at 20 °C. A cable carrying its load runs warmer, and Annex G accounts for that by taking 1.25 × the 20 °C value. Using the cold value would understate the drop by about a fifth.

What standard does this calculator cite? IEC 60364-5-52 Annex G — both the formula and the 3%/5% limits — and its Table 52.2 for the smallest aluminium cross-section.

Assumptions and limits

  • Resistive load (cos φ = 1): the reactance term of Annex G is left out. For conductors up to 50 mm² at an ordinary power factor (around 0.8) the real drop is somewhat lower than shown; the worst case, near cos φ ≈ 0.98, is at most 1.6 % above it (50 mm² copper).
  • ρ₁ is Annex G's service-temperature value for every load; a lightly loaded cable runs cooler and drops a little less.
  • The 3%/5% limits are measured from the origin of the installation: if the feeder to your distribution board already drops some voltage, the circuit itself must stay within what is left.
  • No cable sizing (current-carrying capacity) or breaker selection here — see the cable cross-section calculator.