Ventilation Airflow Calculator

Rooms
Rooms of the dwelling
#1Living room
#2Bedroom
#3Bedroom
#4Kitchen
#5Bathroom
#6WC
#7Hall / corridor
Design

The kitchen, bathroom and WC extract needs the most air, so the supply is raised to match it.

Rates are the residential default values of EN 16798-1 Annex B. The Lithuanian rules (STR 2.09.02:2005 Annex 1, HN 42:2009) could not be checked for this calculator, and your designer may have to apply them instead — they can differ.

Design air flow (supply = extract)162m³/h
Heat-recovery unit capacity, at least194m³/h
Air change rate0.841/h
Air flow per room
Living room (#1) — supply63 m³/h
Bedroom (#2) — supply65 m³/h
Bedroom (#3) — supply34 m³/h
Kitchen (#4) — extract72 m³/h
Bathroom (#5) — extract54 m³/h
WC (#6) — extract36 m³/h
Balance
Floor area of the dwelling74.00 m²
Supply needed for the people137 m³/h
Supply needed for the floor area112 m³/h
Extract needed from kitchen, bathroom, WC162 m³/h
Design air flow = the largest of the three162 m³/h
Air change rate n = flow / volume0.84 1/h
Unit capacity = design flow + reserve194 m³/h

Standards applied: LST EN 16798-1 Annex B


About this calculator

A home with mechanical ventilation — typically a heat-recovery unit (MVHR) — supplies fresh air to the living room and bedrooms and extracts stale, moist air from the kitchen, bathroom and WC. This calculator works out how much air each room needs, balances supply against extract, and gives the air change rate and the capacity of unit to look for.

Which rules. The Lithuanian requirements (STR 2.09.02:2005 Annex 1 and the hygiene norm HN 42:2009) could not be verified for this calculator, so it uses the default values for residential buildings in EN 16798-1 Annex B (in Lithuania LST EN 16798-1). Your ventilation designer may have to apply the Lithuanian figures instead; they can differ.

Formula

EN 16798-1 Annex B defaults (l/s):

Supply:

Cat. Per m² of dwelling Per person Per person, bedroom
I 0.49 (≈ 0.7 1/h) 10 10
II 0.42 (≈ 0.6 1/h) 7 8
III 0.35 (≈ 0.5 1/h) 4 4

Extract:

Cat. Kitchen Bathroom WC
I 28 20 14
II 20 15 10
III 14 10 7
S = max(Σ people × q_person,
        A_dwelling × q_m²)      supply
E = Σ wet-room extract rates    extract
Q = max(S, E)                   supply = extract
room supply  = people's need
             + (Q − Σ need) × A_room / A_habitable
room extract = rate × Q / E
n    = Q / (A_dwelling × h)     air changes, 1/h
unit = Q × (1 + reserve)

The whole-dwelling and per-person rows were read in EN 16798-1 Table B.11 as reproduced by the EU JRC; the bedroom and extract rows were read in REHVA Journal's reproduction of the draft standard's Annex B. How the surplus air is shared between rooms is this calculator's own choice: every habitable room keeps at least its per-person air, the rest goes by floor area.

Worked example

A 74 m² two-bedroom flat, category II: living room 25 m² (2 people), bedrooms 14 m² (2) and 10 m² (1), kitchen, bathroom, WC and an 8 m² hall:

people:  2 × 7 + 2 × 8 + 1 × 8 = 38 l/s
area:    74 × 0.42 = 31.1 l/s          → supply needed 38 l/s
extract: 20 + 15 + 10 = 45 l/s         → design flow 45 l/s = 162 m³/h
living room 14 + 7 × 25/49 = 17.6 l/s = 63 m³/h
bedroom 1   16 + 7 × 14/49 = 18.0 l/s = 65 m³/h
bedroom 2    8 + 7 × 10/49 =  9.4 l/s = 34 m³/h
kitchen 72, bathroom 54, WC 36 m³/h
n = 162 / (74 × 2.6) = 0.84 1/h;  unit with 20 % reserve: 194 m³/h

Here the extract from the wet rooms governs, so the bedrooms and living room get somewhat more than the people alone would need.

FAQ

Which category should I choose? Category II is EN 16798-1's normal level for new buildings. Category I is for higher expectations; III is a moderate level, intended mainly for existing buildings.

Why is supply equal to extract? A heat-recovery unit runs balanced: what it blows in it also draws out, and the heat exchanger needs both streams. The calculator therefore takes the larger of the two needs for both.

What capacity should the unit have? At least the design flow, plus a reserve — at full speed units are noisy and less efficient, and the ducts add pressure loss. The 20 % default is a planning margin you choose, not a figure from a standard; check the unit's fan curve at your duct system's pressure drop.

Is the kitchen hood included? No. A cooker hood is usually a separate extract run only while cooking; the kitchen figure here is the continuous ventilation extract.

Assumptions and limits

  • EN 16798-1 Annex B default values, not the Lithuanian STR/HN figures, which could not be verified. Check them with your designer.
  • The extract rates and the bedroom rate were verified only in a reproduction of the draft standard.
  • Supply in habitable rooms, extract from kitchen, bathroom and WC; halls and corridors only count towards the floor area (transfer air).
  • Room shares of surplus air are this calculator's own rule.
  • No duct sizing, pressure loss, boost mode, cooker hood, or infiltration allowance is included.