Waste Water Flow and Stack Size Calculator

Sanitary appliances on the stack
Building use and stack
Branch fittings into the stack

A stack serving WCs often has a minimum size, set by national rules or the WC manufacturer, larger than the flow alone needs – check it before choosing the pipe.

Discharge units are the System I values (one discharge stack, branch pipes partly filled). Systems II–IV use different values.

Standard: LST EN 12056-2

K × √ΣDU is below the largest single appliance's 2 l/s, so that value is used instead.

The stack size assumes primary ventilation only (the stack carried up through the roof). Horizontal branch and collecting drains are sized separately, from their gradient and filling.

Design waste water flow2.00l/s
Smallest stack size, DN80
Sum of discharge units ΣDU8.8
Waste water flow
Sum of discharge units ΣDU8.8
Frequency factor K0.5
K × √ΣDU1.48 l/s
Largest single appliance (DU)2.0 l/s
Waste water flow Qww2.00 l/s
Continuous flow Qc0 l/s
Total flow Qtot = Qww + Qc2.00 l/s
Discharge stack
Stack size, DN80
Stack capacity Qmax2.0 l/s
Stack utilisation Qtot ÷ Qmax100 %

Standards applied: LST EN 12056-2


About this calculator

This calculator works out the waste water flow that the sanitary appliances connected to one soil stack produce, by the discharge-unit method of LST EN 12056-2, and the smallest discharge stack (DN) that carries that flow with primary ventilation only.

Every appliance type has a discharge unit (DU) – its typical discharge in l/s. Because not all appliances drain at the same time, the flow is not the plain sum of the DUs: it grows with the square root of the sum, scaled by a frequency factor K that depends on how intensively the building is used.

  • Appliances – count the wash basins, showers, baths, sinks, dishwashers, washing machines and WCs that drain into the stack.
  • Building use – a home or an office is intermittent use (K 0.5); a hotel, school or restaurant is frequent use (K 0.7).
  • Branch fittings – swept tees (with an inner radius) let the same stack carry more than square tees.

Formula

ΣDU  = Σ (number of appliances × DU)
Qww  = K × √ΣDU, but at least the largest single appliance's DU
Qtot = Qww + Qc  (continuous flow, if any)
DN   = the smallest stack whose Qmax ≥ Qtot

Discharge units (System I, l/s): wash basin or bidet 0.5, shower without plug 0.6, bath 0.8, kitchen sink 0.8, household dishwasher 0.8, washing machine up to 6 kg 0.8, WC with a 6 l or 7.5 l cistern 2.0, WC with a 9 l cistern 2.5.

Stack capacity Qmax with primary ventilation only (square / swept tees, l/s): DN 60 0.5 / 0.7, DN 70 1.5 / 2.0, DN 80 2.0 / 2.6, DN 90 2.7 / 3.5, DN 100 4.0 / 5.2, DN 125 5.8 / 7.6, DN 150 9.5 / 12.4, DN 200 16.0 / 21.0.

Worked example

A stack in a block of 20 flats; each flat has a wash basin, shower, kitchen sink, dishwasher, washing machine and a 6 l WC. Intermittent use, square tees.

DU per flat = 0.5 + 0.6 + 0.8 + 0.8 + 0.8 + 2.0 = 5.5
ΣDU         = 20 × 5.5 = 110
Qww         = 0.5 × √110 = 5.24 l/s   (more than 2.0, so the formula governs)
DN 100      carries 4.0 l/s  – too little
DN 125      carries 5.8 l/s  – enough → DN 125

For a single house (two basins, shower, bath, sink, dishwasher, washing machine, two WCs) ΣDU = 8.8 and K × √ΣDU = 1.48 l/s – less than one WC's 2.0 l/s, so 2.0 l/s is used.

FAQ

Why is the flow not simply the sum of all appliances? Appliances rarely drain at the same moment. EN 12056-2 accounts for that with the square root of the summed discharge units, multiplied by the frequency factor K.

Does this size the horizontal drains too? No. Branch and collecting drains are sized from their gradient and filling degree, which this calculator does not cover. It gives the vertical stack only.

What does DN mean for a plastic pipe? DN is the nominal size used in EN 12056-2's tables. Plastic drainage pipes are sold by outside diameter; the pipe system's own standard or catalogue says which pipe meets a given DN.

My result is DN 80 but I have WCs – is that enough? By flow, possibly. Many national rules and WC manufacturers set a larger minimum for stacks serving WCs, so check that rule as well.

Assumptions and limits

  • System I discharge units (one discharge stack, branch pipes partly filled).
  • Stack with primary ventilation only; secondary ventilation is not covered.
  • Appliances not listed (floor gullies, urinals, larger washing machines) are not included.
  • The standard's text was not read directly; the values were checked against two independent reproductions of its tables.